LEVELUPS SERIES 10-20 KVA EXPLANATIONS OF LOGGING
AG-SD-83 / Publication Date: 15.09.2014 / Rev. No: 0 / Rev. Date:
Bypass voltage value is out of limit while UPS was operating on the bypass
mode.UPS will switch to normal mode if temperature and load status are
normal.If not ,UPS will stop.
Bypass frequency value is out of limit while UPS was operating on the bypass
mode.UPS will switch to normal mode if temperature and load status are
normal.If not ,UPS will stop.
Over temperature is observed for UPS’ inverter and rectifier coils.
Inverter voltage is out of limit. Load will be transferred to bypass line ,when
inverter voltage gets back to normal values,UPS will switch to normal mode
again.
Output load value is over %105, overloading counter will start to count , If UPS
is on normal mode , the charging will be stopped until load value gets back to
normal.
Maintenance bypass switch is deactivated.
UPS ambient temperature has got back to allowed limit values.
Mains voltage is in the limited values , UPS will switch to normal mode.
Inverter temperature is in the limited values .If load and temperature values
are normal, UPS will switch to normal mode.
Rectifier temperature is in the limited values .If load and temperature values
are normal, UPS will switch to normal mode.
Charger/booster module temperature is in the allowed limits , charging will be
activated again.
Temperature of Static transfer switches is in the allowed limit.
Bypass voltage is within defined limits.
Bypass frequency is within defined limits.
UPS inverter or rectifier coil temperature has got back to normal values.
Inverter voltage is in the limited values , UPS will switch to normal mode.
Output load is under %100 , If charging was OFF , It will be ON .
UPS has detected short circuit at bypass L1 thyristor.UPS will shut down.
UPS has detected short circuit at bypass L2 thyristor.UPS will shut down.
UPS has detected short circuit at bypass L3 thyristor.UPS will shut down.
UPS has detected short circuit at inverter L1 thyristor.UPS will shut down.
UPS has detected short circuit at inverter L2 thyristor.UPS will shut down.
UPS has detected short circuit at inverter L3 thyristor.UPS will shut down.
UPS has detected that inverter L1 thyristor can not be activated.Load will be
transferred to bypass line.
UPS has detected that inverter L2 thyristor can not be activated.Load will be
transferred to bypass line.