SETTINGS
6 SETTINGS
The Mass Combi is provided with two groups of DIP switches to adjust the apparatus according to the specifications of the
electrical installation. The DIP switches are located in the connection compartment. See figure 22.
SW
ON
OFF
1 2 4 6 53 7
8
DIP switch A
SW
ON
OFF
1 2 4 6 53 7
8
DIP switch B
Figure 22: DIP switches
6.1 DIP SWITCH A
6.1.1 Parallel mode
No function
6.1.2 Output frequency inverter
If you want… DIP switch A
SW3
to set the output frequency to 50 Hz OFF
to set the output frequency to 60Hz ON
6.1.3 Energy saving mode
See section 3.2.2 for more information.
If you want… DIP switch A
SW4 SW5
High Power (Energy saving disabled). OFF OFF
Idle 40VA. When it detects a load that is >40VA, it switches on the output power automatically. ON OFF
Idle 150VA. When it detects a load that is >150VA, it switches on the output power automatically OFF ON
Economy 208V. The output voltage will drop to 208V as long as the connected load stays below 250VA. ON ON
26 EN / Mass Combi 12/1200-60 & 24/1200-35 / EN