i-32V5 MIDI Chillers and Inverter Air/Water heat pumps with axial fan
10
SPECIFIC R32 GAS WARNINGS
The R32 refrigerant gas:
is odourless;
is ammable, but only if there are naked ame;
it may cause an explosion, but only if a given concentraon in air is reached.
It is a good pracce to follow these guidelines:
do not smoke near the unit;
ax a no smoking sign near the unit;
keep the premises where the unit is installed properly aerated;
do not pierce or burn the unit;
do not place the unit near ignion sources, such as naked ames, electric heaters etc.;
every extraordinary maintenance or repair on the unit must be performed by skilled technicians or qualied personnel;
a gas leak test must be performed aer installaon.
R32 GAS CHARGE

ensure the R32 is not contaminated by any other types of refrigerant;
keep the gas cylinder in an upright posion when charging;
apply the appropriate label on the unit aer charging;
do not charge more refrigerant gas than needed
when charging is completed, perform leak tests before the operang test
once all the above operaons have been completed, a second leak test should be performed
R32 GAS DISPOSAL

do not dispose of the gas in areas at risk of explosive mixtures forming with air The gas should be disposed of in an appropriate torch with
backring stop device. Contact the supplier should you require operang instrucons.
SAFETY RULES FOR R32 GAS TRANSPORT AND STORAGE
Before opening the unit’s packaging, ensure there are no gas leaks in the environment with an appropriate gas detector. Ensure there are no re
ignion sources near the unit.
No smoking is allowed near the unit.
Transport and storage must be performed in accordance with the naonal regulaons in force. Specically, according to ADR provisions, the total
maximum quanty by transport unit in terms of net mass for ammable gases is 333 kg.
5. INSTALLATION



GENERAL
When installing or intervening on the chiller unit, it is necessary to strictly follow the rules listed in this manual, to observe all the indicaons on
the unit and however to take all possible precauons. Failure to comply with the rules reported on this manual can create dangerous situaons


The company must be informed, within 8 days, of the extent of the damage. The Customer should prepare a wrien statement of any severe
damage.






