The following are the recommended and mandatory acvies for correct operaon of the unit. The mandatory acvies must be carried out
by an authorised customer service which issues a corresponding cercate. Failure to comply with these acvies will entail forfeiture of the
warranty and could considerably shorten the service life of your product.
OPERATION
1
mese
4
mesi
6 mesi
12
mesi
Filling the water circuit x
Presence of bubbles in the water circuit. x
Check the proper working of the safety and control devices.. x
Check that there are no oil leaks from the compressor. x
Check if there is a possible water leakage from the water circuit x
Check that the ow switch works properly. x
Check that the crankcase heaters are powered and running. x
Clean the metal lters of the water circuit. x
Clean the nned coil with compressed air or water jet. x
Check that the electric terminals both inside the electric panel and in the terminal blocks of the compressor are
well ghtened.
x
Tightening of plumbing connecons. x
Check xing and balancing of the fans. x
Clean the air lters in the electrical panel or replace them if necessary.(when present) x
Correct electrical voltage and phase imbalance (without load and under load). x
Correct absorpon. x
Check the refrigerant charge and eventual refrigerant leaks. x
Check the operang pressure, superheang and sub-cooling. x
Circulaon pump eciency. x
If the unit is to be out of service for a long period, drain the water from the pipes and the heat exchanger. This
operaon is indispensable if, during the shutdown period, ambient temperatures are expected to be below the
freezing point of the uid used.
x
Check the presence of corrosion/ossidaon x
Check panel fastening. x
Check the water quality (see chapter Characteriscs of the system water) and the possible concentraon of
glycol
x
Check the pressure drop of any lter driers on the liquid line. x
Check the hydronic side safety valve x
CLEANING THE FINNED COIL
To correctly clean the coil, follow the instrucons below:
Remove any supercial lth. Debris such as leaves, bres etc. must be removed without a vacuum cleaner (use a brush or another so tool
carefully avoiding scratching with metal or abrasive parts). If you use compressed air, pay aenon to keep the air ow perpendicular to the
surface of the coil in order not to bend the aluminium ns. Pay aenon not to bend the ns with the nozzle of the compressed air lance.
Rinse. Rinse with water. It is possible to use chemical substances (specic detergents for nned coils). Rinse the coils by leng the water run
inside each individual passage of the ns, unl they are perfectly clean. Pay aenon to direct the water jet perpendicular to the surface
of the coil in order not to bend the aluminium ns. Do not strike the coil with the water hose. Apply your thumb at the end of the hose to
increase the pressure of the water jet instead of using specic nozzles which could damage the coil..

The an-corrosion treatment applied to the nned coils (available as an alternave to the standard coils) guarantees protecon against aggres-
sive atmospheres.
The frequency of cleaning depends on the environmental condions and is le to the common sense of the maintenance sta. When oxidizing
dust or grease parcles are observed on the baery surface, cleaning is recommended. In general, in a slightly polluted atmosphere, it is recom-
mended to carry out the cleaning treatment every three months.
Washing should be carried out with preferably hot water (40-60 ° C) and detergent with neutral pH, while rinsing is carried out with abundant
fresh water (50 l / m2).
If the maintenance sta observes a lack of protecve cover on the edge of the ns, it is necessary to contact the nearest service center to pro-
ceed with a new applicaon of the cover and completely restore the protecon against corrosion.