i-32V5 MIDI Chillers and Inverter Air/Water heat pumps with axial fan
34
12. TECHNICAL DATA
TECHICAL SHEET i
TECHNICAL CHARACTERSTICS Unità
i-32V5C MIDI
0121 0126 0132
Cooling
Cooling capacity (1) min/nom/max kW
7,8 / 20,7 /
24,7*
8,8 / 25,9 /
27,1*
10,1 / 28,1 /
30,8*
11,2 / 31,8 /
32,8*
Power input (1) kW 6,01 8,15 8,29 10,2
E.E.R. (1) W/W 3,44 3,18 3,39 3,13
Cooling capacity (2) min/nom/max kW
11,4 / 21,6 /
24,7*
12,9 / 25,7 /
27,4*
14,6 / 28,4 /
31,9*
16,3 / 32,8 /
34,3*
Power input (2) kW 4,40 5,44 5,77 7,09
E.E.R. (2) W/W 4,91 4,72 4,92 4,63
SEER (3) W/W 5,22 5,00 5,43 5,06
IPLV (4) 5,53 5,53 5,73 5,54
Water ow rate (1) L/s 1,0 1,2 1,3 1,5
User side heat exchanger pressure drops (1) kPa 37,3 53,6 39,2 47,8
Compressor
Type Twin Rotary DC Inverter
Number of compressors 1 1 1 1
Refriferant oil (type) FW68S or equivalent
Refrigerant oil (quanty) L 1,5 1,5 1,5 1,5
Refrigerant circuits 1 1 1 1
Refrigerant
Type R32 R32 R32 R32
Refrigerant charge (5) kg 1,8 1,8 2,2 2,2
Amount of refrigerant in equivalent CO2 tonnes
(5)
ton 1,22 1,22 1,49 1,49
Design pressure (high/low) chiller mode bar 42,8/3,5 42,8/3,5 42,8/3,5 42,8/3,5
Type Motore DC Brushless
Number 1 1 1 1
Nominal power (1) kW 0,40 0,56 0,70 0,73
Maximum power input kW 1,25 1,25 0,83 0,83
Maximum current input A 2,0 2,0 1,45 1,45
Nominal air ow rate m3/h 8476 9418 12873 12836
Internal heat
Type of internal heat exchanger A piastre
N° internal heat exchangers 1 1 1 1
Water content L 1,7 1,7 2,1 2,1
Useful head (1) kPa 79,0 55,0 66,3 50,2
Water content of hydronic circuit L 2,4 2,4 3,4 3,4
Maximum pressure hydronic kit (safety valve
calibraon)
bar 6 6 6 6
Hydraulic connecons inch 1"M 1"M 1"1/4 M 1"1/4 M
Minimum water capacity (6) L 110 110 110 110
Maximum circulator power kW 0,31 0,31 0,31 0,31
Max. circulator current input A 1,37 1,37 1,37 1,37
Circulator Energy Eciency Index (EEI) ≤ 0,23 ≤ 0,23 ≤ 0,23 ≤ 0,23
Noise level Sound power level Lw (7) dB(A) 72 73 75 77
Power supply 400V/3P+N+PE/50Hz
Maximum power input kW 12,2 10,9 12,7 14,5
Maximum current input A 17,7 15,7 18,3 20,9
Maximum power input with anfreeze kit kW 12,3 10,9 12,8 14,6
Maximum current input with anfreeze kit A 17,7 15,7 18,3 20,9
(1) Cooling: outdoor air temperature 35°C; in/out water temperature 2/7°C.
(2) Cooling: outdoor air temperature 35°C; in/out water temperature 23/18°C.
(3) Cooling: in/out water temperature 7/12°C.
(4) Calculated using AHRI 551/591 (SI) standard.
(5) Indicave data subject to changes. For the correct value, always refer to the technical label on the unit.
(6) Calculated for a decrease in system water temperature of 10°C with a defrost cycle lasng 6 minutes.
(7) Sound power: condion (3); value determined on the basis of measurements made in accordance with UNI EN ISO 9614-2, in compilance with
the requirements of Eurovent cercaon.
(*) acvang the maximum Hz funcon