i-32V5 MIDI Chillers and Inverter Air/Water heat pumps with axial fan
36
(1) Cooling: outdoor air temperature 35°C; in/out water temperature 12/7°C.
(2) Cooling: outdoor air temperature 35°C; in/out water temperature 23/18°C.
(3) Heang: outdoor air temperature temperatura aria esterna 7°C b.s. 6°C b.u.; in/out water temperature 30/35°C.
(4) Heang: outdoor air temperature 7°C b.s. 6°C b.u.; in/out water temperature 40/45°C.
(5) Cooling: in/out water temperature 7/12°C.
(6) Heang: medium cliac condions; Tbiv=-7°C; in/ out water temperature 30/35°C.
(7) Indicave data subject to changes. For the correct value, always refer to the technical label on the unit.
(8) Calculated for a decrease in system water temperature of 10°C with a defrost cycle lasng 6 minutes.
(9) Sound power: condion (3); value determined on the basis of measurements made in accordance with UNI EN ISO 9614-2, in compilance with
the requirements of Eurovent cercaon.
(*) acvang the maximum Hz funcon
-
UNIT AND AUXILIARY ELECTRICAL DATA
Unit power supply V/~/Hz 400/3PH+PE/50
On board controller circuit V/~/Hz 12/1/50
Remote controller circuit V/~/Hz 12/1/50
Fans power supply V/~/Hz 400/3PH+PE/50
applied on the right side panel of the unit.
13. OPERATING LIMITS
EVAPORATOR WATER FLOW RATE
he nominal water ow rate refers to a 5°C temperature dierence between the evaporator inlet and outlet. The maximum permied ow rate
features a 3°C temperature dierence while the minimum one has an 8°C temperature dierence at the nominal condions as shown in the
technical sheet.
For greater details, we have aached a table below with the minimum ow rates for the plate heat exchanger to guarantee proper operaon
according to the model (please note: the water ow switch is applied to protect against failed triggering of the anfreeze probe due to the lack
of ow but does not guarantee the minimum water ow rate required for correct operaon of the unit).
Model
i-32V5C i-32V5H
0121 0126 0132 0121 0126 0132
Minimum water ow to be assured in
chiller mode (condion (1) technical
sheet) [l/s]
0,618 0,773 0,839 0,950 0,529 0,558 0,723 0,776
Maximum water ow to be assured
in chiller mode (condion (1) techni-
cal sheet) [l/s]
1,65 2,06 2,24 2,53 1,41 1,49 1,93 2,07
Minimum ow switch water ow
rate* [l/s]
0,445 0,445 0,528 0,528 0,445 0,445 0,528 0,528
Maximum ow switch water ow
rate* [l/s]
0,477 0,477 0,588 0,588 0,477 0,477 0,588 0,588
* When the ow rate drops below the indicated limit (ow switch minimum water ow rate) the ow switch issues an alarm, which may be reset
only upon reaching the maximum indicated ow rate.
A minimum temperature of 5°C is allowed at the evaporator outlet for standard units. For BT units (low temperature) minimum temperature is
-8°C. In this case glycol water must be used. A maximum temperature of 22°C can be maintained at the evaporator outlet in steady-state oper-
aon.
When the system has reached steady state, the water inlet temperature must not drop below 25°C: lower values, not due to transient phases
or reaching steady-state, can cause system failures and could possibly break the compressor. The maximum outlet water temperature must not
exceed 60°C.
There could be failures to the regular operaon of the unit or, in more crical cases, the safety devices could be triggered due to temperatures
higher than those indicated, especially if coupled with reduced water ow rates.