i-32V5 MIDI Chillers and Inverter Air/Water heat pumps with axial fan
AMBIENT AIR TEMPERATURE AND SUMMERISED TABLE
The units are designed and built to operate in summer mode, with condensaon control, at outdoor air temperatures between -10°C and 48°C. I
heat pup mode, the allowed temperature range of the outdoor air is from -20°C to +35°C depending on the outlet water temperature as shown
in table below.
Room temperature Minimum -15°C Maximum 48°C
Water outlet temperature standard version Minimum 5°C Maximum 22°C
Water outlet temperature LV version Minimum -8°C Maximum 22°C
Heat pump mode
Room temperature Minimum -20°C Maximum 35°C
Outlet water temperature Minimum 25°C Maximum 60°C
Room temperature with water at maximum 44°C Minimum -20°C Maximum40°C
Room temperature with water at maximum 60°C Minimum-7°C Maximum 26°C
Outlet water temperature Minimum 25°C Maximum 60°C
The following are the graphical operang limits for air-condioning and domesc hot water producon.
HEAT PUMP MODE
15
20
25
30
35
40
45
50
55
60
65
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40
Tw [°C]
Ta [°C]
Envelope hea�ng
CHILLER MODE
-10
-5
0
5
10
15
20
25
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55
Tw [°C]
Ta [°C]
Envelope cooling
Cooling Cooling BT