i-32V5 MIDI Chillers and Inverter Air/Water heat pumps with axial fan
18
MAXIMUM CHEMICAL-PHYSICAL PROPERTIES ALLOWED FOR THE CIRCUIT WATER
Manganese (Mn) < 0,05 ppm
Iron (Fe) < 0,3 ppm
Alkalinity (HCO3) 70 – 300 ppm
Chloride ions (Cl-) < 50 ppm
Sulphate ions (SO4) < 50 ppm
Sulphide ions (S) None
Ammonium ions (NH4) None
Silica (SiO2) < 30 ppm
Herein below the hydraulic diagrams for connecon to the unit
KA1
DV1
RV1
FC1
AV1
TE
IN1
P1
EV1
TE
OUT1
LEGEND
EV 1 PLATE HEAT EXCHANGER W-IN WATER INPUT
DV 1 DISCHARGE VALVE W-OUT WATER OUTPUT
RV 1 RELIEF VALVE P 1 ELECTRONIC CIRCULATOR
TE IN 1
WATER INLET TEMPERATURE PROBE-
SONDA
AV 1 AUTOMATIC AIR VENT VALVE
TE OUT 1
USER OUTLET WATER TEMPERATURE
PROBE
FC 1 FLOW SWITCH
--- Accessorio installato a bordo
In each unit a safety valve with 6 bar opening pressure included all the same
The units all of them adopt drainage holes on the basement for the condensate draining which can leach from the pipes of hydraulic and refrig-
erant circuits, and to discharge the generated water during defrosng cycles.