22 AGZ 010B through 034B IOMM AGZB1
Table 10, Field Wiring Data, R-22
Wiring to
Standard Power Block Terminal
Wiring to
Optional Disconnect Switch
Wiring to High Interrupt
or HSCCR Circuit Breaker
AGZ
Unit
Size
Volts
Maximum
Terminal Amps
Connector Wire
Range
(Copper Wire Only)
Disconnect
Size
Connector Wire
Range
(Copper Wire Only)
Max.
Amps
Connector Wire
Range
(Copper Wire Only)
208 175
14 AWG – 2/0 60
14 AWG – 1 AWG
90 10 AWG - 1/0
230 175
14 AWG – 2/0 60 14 AWG – 1 AWG 80 10 AWG - 1/0
460 175
14 AWG – 2/0 60 14 AWG – 1 AWG 40 10 AWG - 1/0
010B
575 175
14 AWG – 2/0 60 14 AWG – 1 AWG 35 10 AWG - 1/0
208 175
14 AWG – 2/0 100
8 AWG - 1/0
125 3 AWG - 3/0
230 175
14 AWG – 2/0 100
8 AWG - 1/0
125 3 AWG - 3/0
460 175
14 AWG – 2/0 60 14 AWG – 1 AWG 60 10 AWG - 1/0
013B
575 175
14 AWG – 2/0 60 14 AWG – 1 AWG 50 10 AWG - 1/0
208 175
14 AWG – 2/0 100
8 AWG - 1/0
125 3 AWG - 3/0
230 175
14 AWG – 2/0 100
8 AWG - 1/0
125 3 AWG - 3/0
460 175
14 AWG – 2/0 60 14 AWG – 1 AWG 70 10 AWG - 1/0
017B
575 175
14 AWG – 2/0 60 14 AWG – 1 AWG 50 10 AWG - 1/0
208 175
14 AWG – 2/0 125
3 AWG – 3/0
175 6 AWG - 350 kcmil
230 175
14 AWG – 2/0 125
3 AWG - 3/0
175 6 AWG - 350 kcmil
460 175
14 AWG – 2/0 60 14 AWG – 1 AWG 80 10 AWG - 1/0
020B
575 175
14 AWG – 2/0 60 14 AWG – 1 AWG 70 10 AWG - 1/0
208 175
14 AWG – 2/0 225
2 AWG - 4/0
200 6 AWG - 350 kcmil
230 175
14 AWG – 2/0 225
2 AWG - 4/0
200 6 AWG - 350 kcmil
460 175
14 AWG – 2/0 100
8 AWG - 1/0
100 10 AWG - 1/0
025B
575 175
14 AWG – 2/0 60
14 AWG – 1 AWG
80 10 AWG - 1/0
208 175
14 AWG – 2/0 225
2 AWG - 4/0
225 6 AWG - 350 kcmil
230 175
14 AWG – 2/0 225
2 AWG - 4/0
225 6 AWG - 350 kcmil
460 175
14 AWG – 2/0 100
8 AWG - 1/0
125 3 AWG - 3/0
029B
575 175
14 AWG – 2/0 100
8 AWG - 1/0
90 10 AWG - 1/0
208 335 6 AWG – 400 kcmil
225
2 AWG - 4/0
N/A Note 1
230 335 6 AWG – 400 kcmil
225
2 AWG - 4/0
N/A Note 1
460 175 14 AWG – 2/0
100
8 AWG - 1/0
150 6 AWG - 350 kcmil
034B
575 175 14 AWG – 2/0
100
8 AWG - 1/0
125 3 AWG - 3/0
NOTES:
1. High Interruptor or HSCCR Circuit Breakers are not available in these sizes
2. "Size" is the maximum amperage rating for the terminals or the main electrical device.
3. "Size" is the disconnect part number and not the amperage rating for the terminals or the main electrical device.
4. "Connection" is the range of wire sizes that the terminals on the electrical device will accept.
5. See page 26 for additional electrical notes.