Operators Guide
The number of compressor stages increases when:
The time since the last stage change exceeds the cooling stage timer AND
Discharge air temperature is greater than the Discharge Cooling Setpoint by more than half
the deadband AND
The current cooling stage is less than the number of available stages AND
The last stage change was a stage up AND
Dehumidification is not active
OR
The time since the last stage change exceeds the cooling stage timer AND
Discharge air temperature is greater than the Discharge Cooling Setpoint by more than half
the deadband AND
The current cooling stage is less than the number of available stages AND
The last stage change was a stage down AND
The Degree Time Above Value is greater than or equal to the Degree Time Below value
AND
Dehumidification is not active
OR
The time since the last stage change exceeds the cooling stage timer AND
Dehumidification is active AND
Leaving Coil Temp is greater than the Maximum leaving coil Setpoint AND
Current Stage is less than the available number of stages
The number of compressor stages decreases when:
The time since the last stage change exceeds the Cooling stage timer AND
Discharge air temperature is less than the Discharge Cooling Setpoint by more than half the
deadband AND
The current cooling stage is greater than zero AND
The last stage change was a stage down AND
Dehumidification is not active
OR
The time since the last stage change exceeds the Cooling stage timer AND
Discharge air temperature is less than the Discharge Cooling Setpoint by more than half the
deadband AND
The current cooling stage is greater than zero AND
The last stage change was a stage up AND
The Degree Time Below Value is greater than or equal to the Degree Time Above value
AND
Dehumidification is not active
OR
The time since the last stage change exceeds the Cooling stage timer AND
Dehumidification is active AND
Leaving Coil Temperature is less than the Minimum leaving coil Setpoint AND
Current Stage is greater than 0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay MicroTech III RAH and is the answer not in the manual?

McQuay MicroTech III RAH Specifications

General IconGeneral
BrandMcQuay
ModelMicroTech III RAH
CategoryController
LanguageEnglish

Related product manuals