40 McQuay OM 920-1
Keypad/Display Menu Structure
Heating Setup Menu
Htg DB is an adjustable item which sets a dead band around the discharge heating setpoint
parameter. For example, if the discharge heating setpoint parameter is set to 100ºF and the Htg
Db= parameter is set to 2ºF, the dead band around the set point would be from 101.0ºF to
99.0ºF.
Htg Period an adjustable item which sets the “sampling time” used in the PI control function
that modulates the heating valve.
Htg Gain is an adjustable item which sets the “proportional band” used in the PI control
function that modulates the heating valve.
Htg PAT is an adjustable item which sets the “project ahead” used in the PI control function
that modulates the heating valve.
Htg Max Chg is an adjustable item that sets the maximum value for an increase or decrease of
the heating valve position.
Stage Time is an adjustable item used to set a minimum time period between heating stage
changes.
OAT Htg Lock is an adjustable item which sets the high outdoor air temperature heating
lockout point. Heating operation is disabled when the outdoor air temperature sensor input
rises above this set point.
OAT Diff is an adjustable item which sets a differential below the OATHtg Lock parameter.
Heating operation is re-enabled when the outdoor air temperature sensor input falls below the
OATHtg Lock value by more than this differential.
F&BP Method is an adjustable item used to set the face and bypass control method. When a
unit equipped with steam or hot water and face and bypass damper, there are two methods
available for controlling the heating arrangement. These are the “Open Valve” and
“Modulating Valve” methods.
F&BP ChgOvrT is an adjustable item used to set the face and bypass changeover
temperature.
Warmup Period is an adjustable item which is used to set the amount of time the gas burner
will remain at a low fire position on 100% OSA units (default 240 seconds).
Hold Period is an adjustable item used to set the amount of time that the gas heating valve
remains at its calculated value on units equipped with 100% OA (default 240 seconds). This is
to allow the temperature to approach equilibrium with the modulating gas heating valve at a
fixed position.
Table 35: Heating Setup Menu
Menu Display Name Item Display Name Default Setting Range Password Level
Heating Setup Htg DB= 2.0°F 1.0-10.0°F 4
Htg Period= 60s 0-999s 4
Htg Gain= 0.8 0.0-100.0 4
Htg PAT= 120s 0-999s 4
Htg Max Chg= 10% 0-100% 4
Stage Time= 5min 2-60min 4
OAT Htg Lock= 55°F 0-100°F 4
OAT Diff= 2°F 0-10°F 4
F&BP Method= OpenVlv OpenVlv 4
ModVlv
F&BP ChgOvrT= 37°F 0-60°F 4
Warmup Period= 240s 0-999s 4
Hold Period= 240s 0-999s 4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay MicroTech III RAH and is the answer not in the manual?

McQuay MicroTech III RAH Specifications

General IconGeneral
BrandMcQuay
ModelMicroTech III RAH
CategoryController
LanguageEnglish

Related product manuals