EasyManuals Logo

McQuay MicroTech III RAH User Manual

McQuay MicroTech III RAH
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #104 background imageLoading...
Page #104 background image
104 McQuay OM 920-1
Operators Guide
Control Temperature is greater than the Zone cooling setpoint by more than half the
deadband AND
Discharge Air Temperature is greater than the minimum DAT cooling setpoint AND
The current cooling stage is less than the available number of stages AND
Dehumidification is not Active
OR
The time since the last stage change exceeds the Cooling stage timer AND
Dehumidification is active AND
Leaving Coil Temp is greater then the maximum leaving coil setpoint AND
Current Stage is less than the available number of stages
The number of Compressor Stages decreases when:
The time since the last stage change exceeds the Cooling stage timer AND
Projected Control Temperature is less than the Zone cooling Setpoint by more than half the
deadband AND
Control Temperature is less than the Zone cooling setpoint by more than half the deadband
AND
The current cooling stage is greater than zero AND
Dehumidification is not Active
OR
The time since the last stage change exceeds the Cooling stage timer AND
Discharge Air Temperature is less than the minimum DAT Cooling setpoint AND
The current cooling stage is greater than zero AND
Dehumidification is not Active
OR
The time since the last stage change exceeds the Cooling stage timer AND
Dehumidification is active AND
Leaving Coil Temperature is less than the minimum leaving coil setpoint AND
Current Stage is greater than 0
Project Ahead
This section provides the Projected Control Temperature used to turn on and off stages of
heating and cooling for Zone Control units. It is not used in DAT units.
In Zone Control cooling and heating operation, the Projected Control Temperature, reduces
overshoot as the zone temperature approaches a setpoint after startup. It does this by causing
stages to stop increasing before the actual Control Temperature reaches the setpoint. The rate
of change of the Control Temperature is calculated once per minute by the controller and
equals the change during the last sixty seconds. This rate of change is multiplied by the
Effective Project Ahead Time and is added to the current Control Temperature. The rate of
change may be negative or positive so the Projected Control Temperature may be higher or
lower than the Control Temperature. This value, the Projected Control Temperature, is the
temperature that would exist after the Project Ahead Time passes if the Control Temperature
were to continue to change at the same rate for the Effective Project Ahead Time. The
Effective Project Ahead Time is set equal to the Cooling Project Ahead Time when a unit with
compressorized cooling is in Cooling State. The Effective Project Ahead Time is set equal to
the Heating Project Ahead Time when a unit with staged heating is in the Heating State. It is
set equal to zero under all other conditions causing the Projected Control temperature to equal
the Control Temperature

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay MicroTech III RAH and is the answer not in the manual?

McQuay MicroTech III RAH Specifications

General IconGeneral
BrandMcQuay
ModelMicroTech III RAH
CategoryController
LanguageEnglish

Related product manuals