Exhaust Fan - Building Static Pressure Control
An Exhaust fan driven by a variable frequency drive is started based on building static
pressure. A constant volume Exhaust Fan is turned on through the same output as the Supply
Fan. An external Fan Delay Relay is used to provide a delay between startups if required.
A VAV exhaust fan is turned on when all four of the following are true:
The Exhaust Fan is controlled by a VFD
The OA Dampers are at least open to the Minimum Exhaust OA Position (default 5%)
The SAF capacity is above the Minimum Exhaust SAF capacity (default 10%)
The building static pressure is above the building static pressure setpoint by more than the
deadband for longer than the Minimum Exhaust Fan Start Time (Default = 120 seconds)
A VAV exhaust fan is turned off when the Supply Fan is turned off or when all three of the
following are true:
The Exhaust Fan is controlled by a VFD
The building static pressure is below the building static pressure setpoint by more than the
deadband OR the OA Dampers are open less than the Minimum Exhaust OA Position
(default 5%). OR the SAF capacity is below the Minimum Exhaust SAF capacity (default
10%)
The Exhaust Fan capacity is at or below its minimum value (Default = 5%) for longer than
the Min Exhaust Fan Stop Time (Default = 120 seconds)
Exhaust Fan - Speed Control
When speed control is selected, the fan operates at the larger of its minimum speed or a value
provided via a connected network or the keypad/display. This value reverts to zero when the
unit is off and remains at that value after startup until a non zero value is written via the
network or the keypad/display.
The exhaust fan is turned on when all four of the following are true:
The Exhaust Fan is controlled by a VFD
The OA Dampers are at least open to the Minimum Exhaust OA Position (default 5%)
The SAF capacity is above the Minimum Exhaust SAF capacity (default 10%)
The Remote Exhaust Fan capacity is commanded to a value above the minimum value
(Default = 5%) by a BAS for longer than the Minimum Exhaust Start Time (Default = 120
seconds)
The exhaust fan is turned off when the Supply Fan is turned off or when both of the following
are true:
The Exhaust Fan is controlled by a VFD
The Remote Exhaust Fan capacity is commanded to less than or equal to its minimum value
(Default = 5%) for longer than the Minimum Exhaust Stop Time (Default = 120 seconds)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay MicroTech III RAH and is the answer not in the manual?

McQuay MicroTech III RAH Specifications

General IconGeneral
BrandMcQuay
ModelMicroTech III RAH
CategoryController
LanguageEnglish

Related product manuals