107
upon 24V/±10V short circuit
0: Activate protection and coast to
stop
1: Alarm and keep running
P97.01
Fault
protection
and alarm
property
setting 2
Fault
protection
and alarm
property
setting 2
Unit place of LED: Action upon
phase loss
0: Activate protection upon input
and output phase loss
1: No protection upon input phase
loss
2: No protection upon output
phase loss
3: No protection upon input and
output phase loss
Tens place of LED: Action upon
loss of external analog
frequency/torque input
0: No action
1: Activate protection and coast to
stop
2: Alarm and keep running
Hundreds place of LED: Action
upon motor overheat
0: Activate protection and
decelerate to stop
1: Activate protection and coast to
stop
2: Alarm and keep running
Thousands place of LED: Action
upon analog input (AI1, AI2) fault
0 : Activate protection and
decelerate to stop
1 : Activate protection and coast
to stop
2 : Alarm and keep running
1 0000 × ×
P97.02
Fault
protection
and alarm
property
setting 3
Fault
protection
and alarm
property
setting 3
Unit place of LED: Action upon
temperature sampling
disconnection
0 : Activate temperature
protection upon inverter and
rectifier module and stop in the
stop mode
1 : Activate temperature
protection upon inverter and
rectifier module and coast to stop
2 : Temperature alarm upon
inverter and rectifier module and
keep running
3 : No action to rectifier, activate
temperature protection upon
1 0000 × ×