Megmeet MV300 Series - Protection and Fault Parameters (Group P97)

Default Icon
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
206
UintTens
Thousands
Action upon contactor abnormality :
0 : Activate protection and coast to stop
1 : Alarm and keep running
Action upon communication fault :
0 : Activate protection and coast to stop
1 : Alarm and keep running
2 : Alarm and stop in the stop mode (only in
serial port control mode)
3 : Alarm and stop in the stop mode (in all
control modes)
Hundreds
Action upon EEPROM abnormality :
0 : Activate protection and coast to stop
1 : Alarm and keep running
Action upon 24V/±10V short circuit :
0 : Activate protection and coast to stop
1 : Alarm and keep running
Fig. 6-74 Fault protection and alarm property setting 1
Fig. 6-75 Fault protection and alarm property setting 2
Fault protection and alarm property setting 3 0~2113H (0000)P97.02
Fault protection and alarm property setting 2 0~2223H (0000)P97.01