207
Fig. 6-76 Fault protection and alarm property setting 3
In certain abnormal situations, the drive can shield faults and stop actions and keep operating by setting
P97.00, P97.01 and P97.02.
The operation panel at that moment will display an alarm AL.XXX (XXX represents the alarm code. For
details, please refer to Chapter 7 Troubleshooting).
P97.00 defines the protection action selections for abnormal communication, abnormal contactor,
abnormal EEPROM and 24V/±10V short circuit.
Note: If "1" is selected for ±10V short circuit action. When a ±10V short circuit fault occurs and lasts, the
drive will automatically report Er.10v after the alarm operates for 15 minutes. When a 24V short circuit
fault occurs, the drive will report Er.24v immediately and stop no matter what 0 or 1 is selected for the
thousands place of P97.00.
P97.01 defines the protection action selections for input/output phase loss, external analog frequency /
torque command loss, motor over-temperature and analog input fault.
P97.02 defines the protection action selections for temperature sampling disconnection, under-voltage
fault, auto reset interval fault and fault locking.
Overload
p
rotection settin
g
fo
r
moto
r
0~2113H
(
0001
)
P97.03