Fault code  Fault type  Possible fault cause  Solutions 
The motor operates at low frequency 
and large load for a long time.   
Add a large fan for the motor to dissipate heat   
Er.AIF 
Abnormal AI 
analog input   
Abnormal control circuit  Seek for service support 
The input analog is out of the range and 
the absolute value is greater than 11V 
Check the analog input   
Er.THI 
Inverter 
module 
temperature 
sampling 
disconnection  
Abnormal temperature sampling circuit  Seek for service support 
The inverter module temperature 
sampling wire is poorly connected.   
Check the inverter module temperature 
sampling wire connection   
Er.THr 
Rectifier 
module 
temperature 
sampling 
disconnection  
Abnormal temperature sampling circuit  Seek for service support 
The temperature sampling wire is poorly 
connected.  
Check the temperature sampling wire connection   
Er.10v 
Control board 
±10V power 
short circuit   
±10Vgrounding    Confirm whether the ±10V wiring is correct   
The interface board circuit is damaged.
Replace the interface board, seek for service 
support 
Er.rEF 
Abnormal 
internal 
over-current 
reference  
The control board circuit is damaged.  Seek for service support 
Er.PIL 
Wrong PID 
limit value 
setting  
The PID lower limit set value exceeds 
PID upper limit set value   
Adjust the PID upper / lower limit set value   
 
All the possible alarm types for MV300 are summarized as shown in table 7-2. For details, please refer to the 
group P97 function code setting. If the fault disappears automatically during the running process, the drive will 
also automatically reset to the status before the alarm (except AL.SC1, for details, please refer to the group 
P97 function code description).
 
Table 7-2    Alarm code table 
Alarm 
code 
Alarm type  Possible alarm causes  Solutions 
AL.oL1 Drive overload  
The motor parameters are incorrect.  Perform the parameter auto-tuning of the motor 
The load is too large.  Adopt the drive with higher power