220 
Alarm 
code 
Alarm type  Possible alarm causes  Solutions 
The DC braking amount is too large. 
Reduce the DC braking current and lengthen the 
braking time 
When instantaneous stop happens, 
restart the rotating motor 
Set the start mode P08.00 as the speed tracking 
restart function 
The acceleration time is too short.  Lengthen the acceleration time 
The grid voltage is too low.  Check the grid voltage   
V/F curve is improper.  Adjust V/F curve and torque increase 
AL.oL2 Motor overload 
The motor overload protection factor 
setting is incorrect. 
Set the overload protection factor of motor correctly. 
The motor is blocked or the sudden 
change of load is too large. 
Check the load 
The universal motor runs at low speed 
for a long time, with heavy load. 
If long-term low-speed running is required, special 
motor should be used. 
The grid voltage is too low.  Check the grid voltage   
V/F curve is improper.  Set V/F curve and torque increase correctly 
AL.EEP 
EEPROM 
read/write  
fault 
The read/write error of the control 
parameters occurs. 
Reset by pressing the STOP/RESET key, seek for 
service support 
AL.SC1 
Abnormal 
serial port 
communication  
The baud rate is set improperly.  Set the baud rate properly. 
Serial port communication error 
Reset by pressing the STOP/RESET key, seek for 
service support 
The fault alarm parameters are set 
improperly. 
Modify the P15.03 and P97.00 settings 
The host device does not work. 
Check if the host device is working and if the wiring is 
correct. 
AL.rLy1 
Abnormal 
contactor  
The grid voltage is too low.  Check the grid voltage 
The contactor is damaged. 
Replace the contactor of the main circuit, seek for 
service support 
The power-up buffer resistance is 
damaged. 
Replace the buffer resistance, seek for service 
support 
The control circuit is damaged.  Seek for service support 
Input phase loss  Check the input R.S.T. wiring