79
2: Continue to run after the
over-torque during running;
3: Turn off the output after the
over-torque is detected only when
the speed is consistent;
4: Turn off the output after the
over-torque is detected during
running;
P06.21
Over-torque
detection
value
Over-torque
detection
value
0.0%~300.0%
SVC: Rated torque of equivalent
motor
V/F: Rated current of equivalent
motor
0.1 0 × × ×
P06.22
Over-torque
detection
time
Over- torque
detection
time
0.0~10.0s 0.1 0.0s × × ×
P06.23
Action
selection for
under-torqu
e detected
Action for
under-torque
detected
0: Under-torque detection is
disabled
1: Continue to run after the
under-torque is detected
only when the speed is consistent;
2: Continue to run after the
under-torque is detected during
running
3: Turn off the output after the
under-torque is detected
only when the speed is consistent;
4: Turn off the output after the
under-torque is detected during
running;
1 0 × × ×
P06.24
Under-torqu
e detection
value
Under-torque
detection
value
0~300.0%
SVC: Rated torque of equivalent
motor
V/F: Rated current of equivalent
motor
0.1% 0%
×× ×
P06.25
Under-torqu
e detection
time
Under-torque
detection
time
0.0~10.0s 0.1 0.0 × × ×
Group P07: VF control parameters
P07.00
Motor 1 V/F
curve
setting
Motor 1 V/F
curve setting
0: User-customized V/F curve
1 ~16: Reserved
17: 2 times power curve
18: 1.7 times power curve
19: 1.2 times power curve
1 0 × √ ×
P07.01
Motor 1 V/F
frequency 3
Motor 1 V/F
frequency 3
P07.03~P03.03 0.01Hz 0.00Hz × √ ×
P07.02
Motor 1 V/F Motor 1 V/F
P07.04~100.0% 0.1% 0.0% × √ ×