81
P07.19
AVR
function
AVR function
0: Disabled
1: Always enabled
2: Disabled only in deceleration
situation
1 2 × ×
P07.20
Drooping
control
value
Drooping
control value
0~30.00Hz 0.01 0.00 ×
Group P08: Start and stop control parameters
P08.00
Startup
mode
Start mode
0: Start from the startup frequency
1: Start form the startup frequency
after braking
2:Start after speed tracking
(including the judgment of
direction)
1 0 × ×
P08.01
Startup
delay time
Startup delay
time
0.00~30.00s
0.01s 0.00s ×
P08.02
Startup
(dwell)
frequency
Startup
frequency
0.00~60.00Hz
0.01Hz 0.00Hz ×
P08.03
Startup
frequency
retention
time
Startup
frequency
retention
time
0.00~10.00s
0.01s 0.00s ×
P08.04
Startup DC
braking
current
Startup DC
braking
current
G: 0.0% ~ 100.0% of the rated
current of the drive
P: 0.0% ~ 50.0% of the rated
current of the drive
0.1%
0.0
×
P08.05
Startup DC
braking time
Startup DC
braking time
0.00 (Disabled)
0.01~30.00s
0.01s 0.00s ×
P08.06 Stop mode Stop mode
0: Decelerate to stop
1: Coast to stop
2:Decelerate to stop + DC braking
1 0 × ×
P08.07
Stop
frequency
detection
Stop
frequency
detection
0.00~150.00Hz
0.01Hz 0.50Hz × ×
P08.08
Stop
frequency
detection
retention
time
Stop
frequency
detection
retention
time
0.00~10.00s
0.01s 0.00s ×
P08.09
Stop speed
detection
mode
Stop speed
detection
mode
0: Speed set value (the only one
detection mode under the V/F
mode)
1: Speed detection value
1 1 × ×
P08.10
Stop (dwell)
frequency
Stop
frequency
0.00~150.00Hz
0.01Hz 02.00Hz × ×