82
P08.11
Stop (dwell)
frequency
retention
time
Stop
frequency
retention
time
0.00~10.00s
0.01s 0.00s × √ ○
P08.12
Initial
frequency
for stop DC
braking
Initial
frequency for
stop braking
0.00~60.00Hz
0.01Hz 0.00Hz × √ ○
P08.13
Waiting time
for stop DC
braking
Waiting time
for stop
braking
0.00~10.00s
0.01s 0.00s × √ ○
P08.14
Stop DC
braking
current
Stop DC
braking
current
G: 0.0% ~ 100.0% of the rated
current of the drive
P: 0.0% ~ 50.0% of the rated
current of the drive
0.1% 0.0% × √ ○
P08.15
Stop DC
braking time
Stop DC
braking time
0.0 (Disabled)
0.01~30.00s
0.01s 0.00s × √ ○
P08.16
Selecting
restart
function
upon power
fault
Restart upon
power fault
0: Disabled
1: Enabled
1 0 × √ ×
P08.17
Waiting time
for restart
upon power
fault
Restart waiti
ng time
0.0~3600.0s
0.1s 0.0s × √ ○
P08.18
Anti-reverse
selection
Anti-reverse
selection
0: Reverse operation is allowed
1: Reverse operation is prohibited
(run at zero frequency upon
reverse running command)
1 0 × √ ×
P08.19
FWD/REV
dead- time
FWD/REV
dead- time
0.00~360.00s
0.01s 0.00s × √ ○
P08.20
FWD/REV
switching
mode
FWD/REV
switching
mode
0: Switch once over the zero
frequency
1: Switch once over the startup
frequency
1 0 × √ ×
P08.21
Use ratio of
dynamic
braking
Use ratio of
braking
0.0~100.0% (0: Disabled) 0.1% 00.0%
× √ ○
P08.22
Braking
startup
voltage
Braking
startup
voltage
700~780
1 750 × √ ○
P08.23
Deceleratio
n time for
emergency
stop
Deceleration
time for
emergency
stop
0.00~100.00s (0: Automatic
high-speed deceleration)
0.01s 0.00s × √ ○
Group P09: Digital input/output parameters