86
setting disconnection
Unit place of LED:
BIT0~BIT3: X1~X4
Tens place of LED:
BIT0~BIT1: X5~X6
P09.16
Virtual input
terminal
setting
Virtual input
terminal
setting
Binary setting:
0: Disabled
1: Enabled
Unit place of LED:
BIT0~BIT3: X1~X4
Tens place of LED:
BIT0~BIT1: X5~X6
1 00 × √ ○
P09.17
Output
selection of
Multi-functio
nal output
terminal Y1
Output
selection of
Multi-function
al output
terminal Y1
0: Open collector output terminal
Y1
1: DO terminal output
1 0
√ √ ×
P09.18
Open
collector
output
terminal Y1
Y1 function
selection
0: Drive in running state signal
(RUN)
1: Frequency arrival signal (FAR)
2: Speed non-zero detection
signal
3: Frequency level detection
signal (FDT1)
4: Frequency level detection
signal (FDT2)
5: Overload detection signal (OL)
6: Lockout for under-voltage (LU)
7: External fault stop (EXT)
8: Frequency upper limit (FHL)
9: Frequency lower limit (FLL)
10: Drive running at zero-speed
11: Simple PLC stage running
completion indication
12: PLC cycle completion
indication
13~14: Reserved
15: Drive ready for running (RDY)
16: Drive fault
17: Host device switch signal
18: Reserved
19: Limiting torque
Torque command is
enabled when limited by the
torque limit value 1 or 2
20: Flux detection signal
Flux detection value is
1 0 √ √ ×
P09.19
Open
collector
output
terminal Y2
Y2 function
selection
1 1 √ √ ×
P09.20
Relay RO1
output
function
selection
RO1 function
selection
1 15 √ √ ×