37
FV36 85-03-01014
LP Gas Pressure Requirements
Inlet and manifold gas pressure checking taps are located on gas valve. These ports are only accessible from
the outer left side of the fireplace. A qualified installer will take pressure measurements at these ports to
verify and set the correct gas pressures during the LP Kit installation and before fascia materials are installed
over the front of this fireplace. Manifold pressure must be taken at the “MANIFOLD PRESSURE" tap and inlet
pressure at the "INLET PRESSURE" tap with the burner operating by a qualified installer.
LP Gas Pressure Requirements
REGULATE THE FLAME HEIGHT TO "HIGH" POSITION. OUTLET GAS PRESSURES MAY VARY PLUS OR MINUS 5%.
LP Gas Proper Input Rates
With the proper orifices installed, as specified above, this fireplace using LP gas will have a maximum input
rate of 44,000 Btu/hr.
Leak Testing Requirements
Prior to completing the conversion process, check for gas leaks with soap and water solution at all plumbing
joints prior to placing this fireplace into operation. It is recommended that all gas-plumbing joints, factory
installed and field installed, are checked for leaks.