EasyManuals Logo

METREL EasiTEST MI 2087 AL2 User Manual

METREL EasiTEST MI 2087 AL2
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
MI 2087 AL2 EasiTEST Measurement instructions
20
Step 8 (looP function is selected)
q Press the START key and release it, the measurement will start to run. Three
dots (. . .) will flash until the measurement is finished, then the result is
displayed. The measurement may last longer (up to 1 min approx.) in order to
assure accurate and stabile test result.
q Check contact voltage subresult (Uc at IN – standard RCD or Uc at 2IN
selective RCD) and preset limit contact voltage by using the DISPLAY key.
Notes:
q If RCD trips during the measurement (some fault or leakage current is probably
already flowing to ground) “rcd mark will start to blink.
q RCD type, limit contact voltage, and nominal differential current set in this
function will be offered in other RCD functions (wherever actual)!
q Current flowing to PE protective conductor, caused by faulty appliances or
capacitive connection between L and PE terminals will influence the test result.
Disconnect such appliances before the measurement is started!
q Specified accuracy of Uc/RL measurement is valid only if earthing system
connected to PE terminal is free of interfering voltages!
q bat” message displayed during or after finishing the measurement means
batteries are too weak to guarantee correct result. Replace the batteries.
3.4 RCD - Trip-out time
In order to assure safe conditions, RCD device must trip-out within a certain time,
in case of present fault on connected electric appliance. See allowed trip-out time
ranges in the following table.
Type of RCD
protection
switch
In 2In 5In* Remark
Standard
300 ms 150 ms 40 ms max. allowed trip-
out time
500 ms 200 ms 150 ms max. allowed trip-
out time
Selective
130 ms 60 ms 50 ms min. allowed trip-
out time
* If IN 30 mA, test current of 0,25 A is used instead of 5IN.
Table 1: Allowed trip-out times according to EN 61009 standard
For additional general information concerning the measurement, refer to enclosed
handbook Measurements on electric installations in practice and theory.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the METREL EasiTEST MI 2087 AL2 and is the answer not in the manual?

METREL EasiTEST MI 2087 AL2 Specifications

General IconGeneral
BrandMETREL
ModelEasiTEST MI 2087 AL2
CategoryTest Equipment
LanguageEnglish

Related product manuals