MI 3295 Step Contact Voltage Measuring System Technical specifications
47
Test signal frequency ...................................... 55 Hz
Influence of probe resistance: ≤ (10 % of reading + 10 digits)
(Rc, Rp)
max
= (10 + 100 R) or 2 k (whichever is lower)
Automatic test of probe resistance.......... yes
Automatic detection of voltage noise.
Test terminals:
10.4 Specific earth resistance (MI 3295S)
Calculated value, consider
accuracy of Resistance to earth
function.
Calculated value, consider
accuracy of Resistance to earth
function.
Wenner method principle with equal distances between test probes:
= 2··distance·R.
10.5 Potential (MI 3295M)
(2 % of reading + 2 dig)
Calculated measuring
range U
*Displayed Potential is obtained on base of calculation:
U
S
=U
m ∙
I
fault
/I
gen