MI 3201 TeraOhm 5 kV Plus Measurements
Set-up parameters for Withstanding Voltage:
- Press the SELECT key, (the set-up menu (Fig. 30)
appears on display);
- Select the parameter (line) to be set using the and
keys;
- Adjust the parameter using the and keys or skip
to the next sub-parameter by pressing the SELECT
key (if there are two or more sub-parameters) and
repeat the adjustment.
- Complete the parameter adjustments by pressing
either the ESC or the START/STOP key (to run the
measurement directly). The settings displayed last will
be saved.
Fig. 30. Set-up menu in
Withstanding Voltage function
Notes:
Tstep and Tend are independent timers. The maximum time for each timer is 30 min
60 s. Tend begins after the completion of the ramp period. Ramp period can be
calculated from:
Tramp Tstep(Ustop – Ustart) / 25 V
If Tstep is set to 00min 00s, then the ramp voltage increases by approximately 25 V
every 2s.
Warning!
Refer to Warnings chapter for safety precautions!