EasyManua.ls Logo

Metso VALVCON V-Series - Verify Zero and Span Settings

Metso VALVCON V-Series
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The Control Board features full reverse acting set up,
requiring no wiring changes. See below for simple Set
Zero and Set Span procedures.
* For 180˚ Rotation order Option Kit P/N VC099180 to
replace 90˚ Potentiometer and Cam Gears.
For 270˚ Rotation order Option Kit P/N VC099270 to
replace 90˚ Potentiometer and Cam Gears.
WARNING
WHEN CONTROL BOARD IS INSTALLED, POWER TO TERMINAL 3
OR TO TERMINAL 4 WILL DAMAGE ELECTRONIC CIRCUIT BOARDS.
POWER TERMINALS 1 AND 2; USE CW CLOCKWISE AND CCW
COUNTERCLOCKWISE BUTTONS TO DRIVE ACTUATOR.
Set Zero:
1. Turn the Mode Selector Dial to [ZERO] and press
[ENTER] for 2 seconds. The Zero LED will begin to ash.
2. Drive the actuator to desired minimum signal position
using the CW or CCW pushbutton. If the “STALL LED
begins to ash; check to see if the limit switch cam is
preventing actuator from reaching desired end-oftravel.
If necessary back the cam o so that it will trip the switch
slightly beyond the desired end-of-travel.
3. Apply input control signal, (i.e. 4 mA).
4. Press the [ENTER] button to save the Zero setting.
Set Span:
1. Turn the Mode Selector Dial to [SPAN] and press
[ENTER] for 2 seconds. The Span LED will begin to ash.
2. Drive the actuator to desired maximum signal position
using the CW or CCW pushbutton. If the “STALL LED
begins to ash; check to see if the limit switch cam is
preventing actuator from reaching desired end-of-
travel. If necessary back the cam o so that it will trip
the switch slightly beyond the desired end-of-travel.
3. Apply input control signal, (i.e. 20 mA).
4. Press the [ENTER] button to save the Span setting.
Verify Zero and Span Settings:
1. Turn the Mode Selector Dial to [RUN].
2. Apply various control signals to verify operation.
3. Replace actuator cover.
3.4.4 Proper Actuator Cover Installation
1. Remove the override shaft from the actuator cover
bushing; if the actuator is equipped with a handwheel,
remove the handwheel before removing the top piece
of the “two-piece shaft from the cover bushing.
Figure 4
IMO 11/17
IMO-I2500 EN 7

Other manuals for Metso VALVCON V-Series

Related product manuals