Remote Power Off communication port (9)
Installation of a Remote Power Off function must be carried out in compliance with applicable regulations.
In order to fully de-energize Pulsar MX RT with the RPO port, it is necessary to use a two-position switch (Normally Open
or Closed contact). Once switch is energized/de-energized, the UPS shuts off the display and the output of the UPS.
◗ The output devices can be powered again through auto bypass when the two-position switch is released (open or closed).
◗ The output devices will remain powered < 1 sec. after RPO activation.
Push the start button to return to normal operation.
Note: The internal batteries will remain connected to the power sub-module after RPO activation.
The cable is not included.
Installation of optional
communication card (66102)
2.6 Required Protective Devices and Cable Cross-Sections
Recommended upstream protection
Required cable cross-sections
◗ Terminal-block cable capacity: 6 mm
2
, solid or stranded wire (maximum AWG 10).
◗ Capacity for earthing conductor: 6 mm
2
, solid or stranded wire (maximum AWG 10).
Remote power off contact normally closed (9)
Remote power off contact normally open (9)
◗ Signal:
activation voltage: 5 V DC to 27 V DC,
current: 10 mA max.