4.4 UPS Set-Up
Local Settings
Output Settings
ON/OFF Settings
Function Factory Setting Options Comments
Cold Start Disabled Enabled
Start on battery
Forced Reboot Enabled Enabled
Enables automatic restart of the
system even if Normal AC source
is restored before the end of the
shutdown sequence
Auto Restart Enabled Disabled
UPS restarts automatically when
Normal AC source is restored
Energy Saving Disabled Enabled
Automatic shutdown on battery if
output load level < 10%
Sleep Mode Enabled Disabled
Remote Command Enabled Disabled
Enables consideration of
shutdown or restart orders from
software to be authorized
Function Factory Setting Options Comments
Output Voltage 208V
200V / 230V / 220V /
240V / 250V
Freq Converter Disabled Enabled
Output Frequency 60 Hz 50 Hz
User selectable under frequency-
converter mode
Eco Mode Disabled Enabled See glossary
Slew rate 1 Hz/sec. 0.5 Hz/sec.
Bypass Transfer Yes No
Transfer to bypass if Normal AC
source is out of tolerance
Interrupt Time 10 ms 20 ms, ...... , 200 ms
Break time calibration during load
transfer on Normal AC source out
of tolerance
Overload Prealarm 105 % 40%, 50%, 70% Alarm if threshold is overrun
Function Factory Setting Options
Language English
French, German, Italian, Portuguese, Spanish
Date/Time Format
International format
(DD-MM-YYYY/HH :MM)
US (MM-DD-YYYY/HH:MM AM/PM)
Date/Time Change
GMT + 1
(Continental Europe)
MM-DD-YYYY/HH :MM adjustable
Audible Alarm Yes No
Pulsar MX
Access to Maintenance and
Personalization Data
4 — 2
86-87050-00 A01