8.1 Technical specifications
(1) If the output voltage is 200V — 250V, the output power is 5000VA / 4500W.
(2) With one EXB module or more, the standard output power is 5000VA / 4000W.
(3) Values for 70% / 100% of UPS output.
(4) Programmable: 200V / 208V / 220V / 230V / 240V / 250V using the Personal Solution-Pac software.
(5) Frequency-converter mode is programmable using the Personal Solution-Pac software.
(6) Step-down transformer is available for 120V output.
Pulsar MX 5000 Pulsar MX EXB
Output power
5000 VA (1) /
4500 W (2)
Electrical supply network
Rated input voltage
Input voltage range
Frequency
Power factor
Leakage current
Single phase 208 V
120/156 V to 280 V (3)
50/60 Hz (autoselect)
> 0.99
7 mA
Load output
Voltage
Frequency
Harmonic distortion
Overload capacity
Single phase 208 V ±3% (4)
50/60 Hz ±0,5% (5)
< 3%
105% continuous, 110% 2min,
125% 1min, > 150% 0.5s
Battery
15 x 12V - 5 Ah,
sealed lead acid,
maintenance free
Two 15 x 12 V - 5 Ah
strings, sealed lead acid,
maintenance free
Environment
Operating temperature range
Relative humidity
Storage temperature range
Altitude
0°C to 40°C
20% to 90% (non-condensing)
-25°C to 40°C
1000 m
Noise level
< 45 dBA