V6R VRF 50/60Hz
165
Part 6 - Diagnosis and Troubleshooting
4.3 Parameters of Excess and Insufficient Refrigerant System
Underthefollowingconditions,theoperatingparametersgiveninTables64.4and64.5shouldbeobserved:
The masteroutdoorunitcandetectalltheindoorunits.
The numberofindoorunitsdisplayedonDSP2issteadyandisequaltotheactualnumberofindoorunitsinstalled.
Allsto
pvalvesareopenandallindoorunitEEVsareconnectedtotheirunit sPCB.
Ifthecombinationratiois100%orless,alltheindoorunitsarecurrentlyrunningandifthecombinationratioismore
than100%,indoorunitswithtotalcapacityequaltothetotalca
pacityoftheoutdoorunitsarecurrentlyrunning.
If the outdoor ambient temperature is high, the system is being run in cooling mode with the following settings:
temperature17°C;fanspeedhigh.
If the outdoor ambient temperature is low, the system is being run in heating mode with th
e following settings:
temperature30°C;fanspeedhigh.
The systemhasbeenrunningnormallyformorethan30minutes.
Thereparametersaremorereliableincooingonlymode.
Table64.4:Outdoorunitoperatingparametersinexcessrefrigerantsystem
Outdoor ambient temperature (T4 ) °C 41 31to41 26to31 10to26
10
Discharge pressure (Pc) MPa 3.5≥3.4≥2.8≥2.6≥2.4
Suction superheat (T7-Te) °C 3≤3≤3≤3≤3
Discharge superheat (DSH) °C 11≤15≤15≤15≤17
Table64.5:Outdoorunitoperatingparametersininsufficientrefrigerantsystem
Outdoor ambient temperature (T4 ) °C 41 31to41 26to31 10to26
10
Discharge pressure (Pc) MPa 3.0≤2.6≤2.4≤2.3≤2.2
Suction superheat (T7-Te) °C 18≥15≥15≥12≥12
Discharge superheat (DSH) °C 35≥35≥30≥30≥30