EasyManuals Logo

Midea VRF Series User Manual

Midea VRF Series
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #122 background imageLoading...
Page #122 background image
V6R VRF 50/60Hz
121
2.17 Hb: Low pressure sensor error
Digital display output
Description
Low pressure sensor error.
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
Trigger condition: The main control board cannot receive the feedback signal of low pressure sensor.
Recover condition: The main control board can receive the feedback signal of low pressure sensor.
Reset method: Resume automatically.
Possible causes
Outdoor unit Low gas stop valves are closed.
Pressure sensor not connected properly or has malfunction.
Outdoor main PCB damaged.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea VRF Series and is the answer not in the manual?

Midea VRF Series Specifications

General IconGeneral
Compressor TypeInverter Scroll Compressor
TypeVariable Refrigerant Flow (VRF)
RefrigerantR410A
ControlCentralized control, individual control
Indoor Unit TypesWall mounted, cassette, ducted, floor standing
Energy EfficiencyHigh energy efficiency with DC inverter technology
Indoor Unit Noise Level19 dB(A) to 45 dB(A)

Related product manuals