V6R VRF 50/60Hz
89
2.3 E2: Communication error between MS box and master unit
Digital display output
Description
Communication error between MS box and master outdoor unit.
All units stop running.
Error code is only displayed on the master unit.
Trigger / recover condition
Trigger condition: MS box and outdoor units cannot communication for 2 minutes after the system power on 20 minutes.
Recover condition: Communication go back to normal.
Reset method: Resume automatically.
Possible causes
Communication wires between MS box and outdoor units not connected properly.
MS box power supply abnormal.
Loosened wiring within electric control box.
The sequence of the PQE signal lines is incorrect.
Interference from high voltage wires or other sources of electromagnetic radiation.
Communication wire too long.
Damaged outdoor main PCB or electric control box communication terminals block.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea VRF Series and is the answer not in the manual?

Midea VRF Series Specifications

General IconGeneral
Compressor TypeInverter Scroll Compressor
TypeVariable Refrigerant Flow (VRF)
RefrigerantR410A
ControlCentralized control, individual control
Indoor Unit TypesWall mounted, cassette, ducted, floor standing
Energy EfficiencyHigh energy efficiency with DC inverter technology
Indoor Unit Noise Level19 dB(A) to 45 dB(A)

Related product manuals