V6R VRF 50/60Hz
102
Midea
V6R
Series Service Manual
2.12 H0: Communication error between main board and compressor drive board
Digital display output
Description
H0 indicates a communication error between main board and compressor drive board.
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Main control board and inverter driver board cannot communication for 2 minutes.
Recover condition: Communication go back to normal.
Reset method: Resume automatically.
Possible causes
Loosened communication wiring from the outdoor main PCB to the inverter module.
Filter board damaged.
Compressor inverter module damaged.
Outdoor main PCB damaged.