V6R VRF 50/60Hz
137
2.25 PL, C7: Inverter module temperature protection
Digital display output
Description
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
Trigger condition:
For PL protection: Refer to Part 3 6.5 Inverter Module Temperature Protection Control
For C7 protection: PL protection appears three times in 100 minutes.
Recover condition:
Refer to Part 3 6.5 Inverter Module Temperature Protection Control
Reset method:
For PL protection: Resume automatically.
For C7 protection: Manually restart.
Possible causes
Blocked, dirty or loose heat sink.
Inverter module damaged.
Procedure
PL / C7
The inverter module heat sink is blocked
or dirty
Yes
Clean or replace the heat sink
No
The screws connecting the heat sink to
the inverter module are loose
Yes
Tighten the screws and make sure the
heat sink is well-connected
No
Replace the inverter module

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea VRF Series and is the answer not in the manual?

Midea VRF Series Specifications

General IconGeneral
Compressor TypeInverter Scroll Compressor
TypeVariable Refrigerant Flow (VRF)
RefrigerantR410A
ControlCentralized control, individual control
Indoor Unit TypesWall mounted, cassette, ducted, floor standing
Energy EfficiencyHigh energy efficiency with DC inverter technology
Indoor Unit Noise Level19 dB(A) to 45 dB(A)

Related product manuals