2.15 H7: Qty. of indoor units mismatching
Digital display output
Description
Number of indoor units detected by master unit not same as number set on outdoor main PCB.
All units stop running.
Error code is only displayed on the master unit.
Trigger / recover condition
Trigger condition: One or more indoor units cannot be detected by master unit for 20 minutes.
Recover condition: Number of indoor units detected by master unit is same as number set on outdoor main PCB for
1minute.
Reset method: Resume automatically.
Possible causes
Number of indoor units set on outdoor main PCB not same as actual number of indoor units.
Some indoor units are powered off.
Communication wires between indoor and outdoor units not connected properly.
Indoor unit PCB damaged.
Indoor unit without address or indoor unit address duplicated.
Outdoor main PCB damaged.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea VRF Series and is the answer not in the manual?

Midea VRF Series Specifications

General IconGeneral
Compressor TypeInverter Scroll Compressor
TypeVariable Refrigerant Flow (VRF)
RefrigerantR410A
ControlCentralized control, individual control
Indoor Unit TypesWall mounted, cassette, ducted, floor standing
Energy EfficiencyHigh energy efficiency with DC inverter technology
Indoor Unit Noise Level19 dB(A) to 45 dB(A)

Related product manuals