EasyManuals Logo

Midea VRF Series User Manual

Midea VRF Series
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #105 background imageLoading...
Page #105 background image
V6R VRF 50/60Hz
104
Midea
V6R
Series Service Manual
2.13 H2, H3: Qty. of outdoor unit decreases/ increases error
Digital display output
Description
H2 indicates Qty. of outdoor unit decreases error.
H3 indicates Qty. of outdoor unit increases error.
All units stop running.
Error code is only displayed on the master unit.
Trigger / recover condition
Trigger condition: Qty. of slave units detected by master unit has decreased or increased.
Recover condition: Qty. of slave units detected by master unit goes back to normal.
Reset method: Resume automatically.
Possible causes
Some outdoor units are powered off.
Power supply abnormal.
Incorrect outdoor unit address setting.
Communication wires between outdoor units not connected properly.
Loosened wiring within electric control box.
Damaged outdoor main PCB or electric control box communication terminals block.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea VRF Series and is the answer not in the manual?

Midea VRF Series Specifications

General IconGeneral
Compressor TypeInverter Scroll Compressor
TypeVariable Refrigerant Flow (VRF)
RefrigerantR410A
ControlCentralized control, individual control
Indoor Unit TypesWall mounted, cassette, ducted, floor standing
Energy EfficiencyHigh energy efficiency with DC inverter technology
Indoor Unit Noise Level19 dB(A) to 45 dB(A)

Related product manuals