EasyManua.ls Logo

Midea VRF Series

Midea VRF Series
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V6R VRF 50/60Hz
157
3.8 F6: Electronic ball valve connection failure (for MS01)
Digital display output
Description
Electronic ball valve (EBVA/EBVB/EBVC) connection failure.
All units stop running.
Error code is displayed on the unit with the error. The indoor unit display board or wired controller connected under
this MS displays "F8" fault code.
Trigger / recover condition
Trigger condition: The main control board cannot receive the feedback signal of EBV.
Recover condition: The main control board can receive the feedback signal of EBV.
Reset method: Manually restart.
Possible causes
Electronic ball valve coil doesn't connect properly or malfunction.
MS PCB damaged.

Table of Contents

Related product manuals