OM-206 360 Page 12
3-4. Positioning Jumper Links
Check input voltage available at
site.
1 Jumper Link Label
Check label - only one is on unit.
2 Jumper Links
Move jumper links to match input
voltage.
All these units are connected on
400 V.
230V
400V
230V
400V
2
1
3-5. Electrical Service Guide
Infinity 35 Infinity 45
Input Voltage 230 400 230 400
Input amperes at rated output 36A 21A 52A 30A
Fuse or circuit breaker rating (max. rec) 36A 21A 51A 29A
Input conductor size* 6 mm
2
6 mm
2
6 mm
2
6 mm
2
Grounding conductor size** 6 mm
2
6 mm
2
6 mm
2
6 mm
2
* Power cord supplied with the unit is sized for 230V operation.
** Larger power cord may be required for cable length greater than 3 meters. Consult national or local regulations.