Parameters P-68 through P-75 are used to stabilize the reading. These are general
purpose parameters, suitable for all applications.
P-68 fill damping
is the maximum rate at which the display reading and analog output will
change under filling conditions. The damping rate is measured in P-1
units per minute and has a range of 0.001 to 9999. Thus the smaller the
number entered, the greater the damping.
enter desired amount (F=10.00 m/min)
P-69 empty damping
is the maximum rate at which the display reading and analog output will
change under emptying conditions. The damping rate is measured in P-1
units per minute and has a range of 0.001 to 9999. Thus the smaller the
number entered, the greater the damping.
enter desired amount (F=10.00 m/min)
P-70 process rate display (V)
display the rate of filling (+) or emptying () in P-1 units/minute. Press
to view while in RUN mode.
P-71 process rate filter
controls the response of the rate display
enter option 0 = continually averaged rate
1 = update rate every minute or 50 mm (F)
2 = update rate every 5 minutes or 100 mm
3 = update rate every 10 minutes or 300 mm
99 = arbitrary settings
this option allows the time or distance variables to be arbitrarily
set via the s and d sub-parameters.
P-71
1 factory setting option
99
99 arbitrary settings selected
s - 71 seconds sub-parameter
7
ENTER
ALT
DISP
*
9
9
PL-399 7 14