10 factory setting, 10 sec
5
5 change to 5 seconds
d-71 distance sub-parameter
0.010 distance in m (units of P-1)
0.005
0.005 change to 0.005
P-72 fuzz filter
the fuzz filter is designed to keep the display constant when minor changes
on the liquid surface (ripples), electrical noise or air movements in the
vessel are occurring.
enter 0 = OFF
1 = ON (F)
P-73 agitator discrimination
enter 0 = OFF
1 = ON (F)
P-74 fail-safe mode
in the event of a loss of echo, the HydroRanger I will flash LOE and go
into one of the following fail-safe modes after the timer (P-75) expires
enter 1 = high
2 = low
3 = hold last entry (F)
P-75 fail-safe timer
the amount of time delay before going into fail-safe mode
enter desired amount of time, in minutes (F=15.00)
e.g.: for 30 sec. time delay, enter 0.5
ENTER
ENTER
ALT
DISP
ALT
DISP
*
5
0
0
.
5
PL-399 7 15