Mirtone QuickStart Front Panel Programming Getting Started Guide 6
Qty Model Description
7 GSA-PS Intelligent photoelectric smoke detectors
4 GSA-IPHS Intelligent 4D multisensor smoke detector
4 GSA-HFS Intelligent fixed temperature heat detector
15 GSA-SB Standard bases for detectors
5 GSA-DH Duct smoke detector housing
5 GSA-PS Intelligent smoke detector (for duct)
5 GSA-SB Standard base
5 73681-? Sampling tube for duct (choose length)
5 GSA-CR Intelligent control relay
5 GSA-CT2 Intelligent dual input module (flow & tamp)
1 GSA-CT1 Intelligent single input module (kitchen hood system)
1 GSA-CT1 Intelligent single input module (monitor Knox box)
4 GSA-CC1 Intelligent single riser NAC module (for floor signal
circuits)
5 GSA-CR
Intelligent control relay module (for elevator recall, shunt
trip, door holder release, alarm light in elevator machine
room
1 MIRBPS6 Six amp booster power supply
25 MG1R-HDVM Genesis multi-cd horn strobe
In our example a MIR-QS4-5 panel was chosen to allow room for future expansion, but a
MIR-QS1, which includes one SLIC module, could also have been used.