Mirtone QuickStart Front Panel Programming Getting Started Guide 9
To AutoLearn the control panel:
1. At the main control panel, press Menu on the keypad.
2. From the Main Menu, choose Login and enter the level 4 password. (Default: 4444.)
3. Choose Reports > Revisions, press Enter to accept Panel ID 01, then choose Display.
Scroll through the list to verify that all the cards installed in the system are listed. If
not, check the connections and repeat steps 1 through 3.
4. Press Menu twice, then choose Program > Configure. Wait for the “System
Initializing SIGA devices” message to clear, then choose AutoLearn.
5. Enter 01 for the Panel ID.
6. Enter the number of panels connected to the RS-485 riser. This includes the main
panel and all remote annunciators.
7. Select the wiring configuration for the RS-485 data line.
8. Press Enter.
The panel database is updated.