EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-F Series - Page 16

Mitsubishi Electric MELSEC iQ-F Series
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
2 SERVO AMPLIFIER SETTING
2.3 Ethernet Parameter Settings
5.
Set as shown below. After the parameters are set, check the connection to the servo amplifiers by clicking
[Communications Test]. When the connection has succeeded, click [OK].
*1 For the fourth octet of IP addresses, the values set by the rotary switches in the step 1 are used. Thus, the IP addresses are as shown
below.
Station number 1: 192.168.3.1
Station number 2: 192.168.3.2
Precautions
When the communication test detects a connection failure, perform the following.
Check the power supplies of the programmable controller and the servo amplifiers, wiring with Ethernet cables.
Check the IP address and the subnet mask of the personal computer.
Initialize the servo amplifiers.
For how to initialize servo amplifiers, refer to the following.
MR-JET-G User's Manual (Introduction) [4.6 Servo amplifier setting initialization]
Item Setting value
Axis 1 Axis 2
Connection Network CC-Link IEF Basic
Via None
PC side I/F Protocol UDP
Time-out 1s
Retry 0 times
Servo Amplifier Configuration Model MR-JET-G MR-JET-G
IP address
*1
192.168.3.1 192.168.3.2