EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-RJ71C24-R2 - Page 505

Mitsubishi Electric MELSEC iQ-RJ71C24-R2
574 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
APPENDICES APPENDIX
Appendix 3 Buffer Memory
503
A
512
(200H)
For confirmation
of station
number setting
status
Station number (parameter setting) Depend
s on
paramet
er
setting
R Page 441 Module
information list
513
(201H)
For confirmation
of LED lighting
status and
communication
error status
CH1 side LED lighting status and
communication error status
0: LED OFF, no error
1: LED ON, error
SD WAIT (b0)
SIO (b1)
PRO. (b2)
P/S (b3)
C/N (b4)
NAK (b5)
ACK. (b6)
NEU. (b7)
For system (b8) to (b14)
CH1 ERR. (b15)
Depend
s on
module
status.
514
(202H)
CH2 side LED lighting status and
communication error status
0: LED OFF, no error
1: LED ON, error
SD WAIT (b0)
SIO (b1)
PRO. (b2)
P/S (b3)
C/N (b4)
NAK (b5)
ACK. (b6)
NEU. (b7)
CH2.ERR. (b14)
For system (b8) to (b13),(b15)
Depend
s on
module
status.
515
(203H)
For confirmation
of parameter
setting and
mode switching
Parameter setting error and mode switching
error status
0: No error
Other than 0: Parameter setting error and
mode switching error
CH1 Communication protocol setting number
(b0)
0: Normal 1: Error
CH1 Communication speed setting (b1)
0: Normal 1: Error
CH1 Mode switching at setting change
prohibit (b3)
0: Normal 1: Error
CH2 Communication protocol setting number
(b4)
0: Normal 1: Error
CH2 Communication speed setting (b5)
0: Normal 1: Error
CH2 Mode switching at setting change
prohibit (b7)
0: Normal 1: Error
Setting station No. (b14)
0: Normal 1: Error
Interlink operation setting (b15)
0: Normal 1: Error
0 R Page 445 Intelligent
function module
monitor
Address
Dec (Hex)
Purpose Name Defaul
t value
Protocol Reference
CH1 CH2 MC Non Bi Pd

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-RJ71C24-R2

Related product manuals