20 USING SEND/RECEIVE DATA MONITORING FUNCTION
20.2 Send/receive Data Monitoring Function Settings
391
20
Buffer memory for send/receive data monitoring function
Send/receive data monitoring designation (Un\G8216/8472)
Designate the start/stop of the send/receive data monitoring function.
For details on the send/receive data monitoring designation operation, refer to the following section.
Page 388 Send/receive data monitoring operation
Monitor option specification (Un\G8217/8473)
Designate the options of the send/receive data monitoring function.
Stop at buffer full specification (bit 0)
When the stop at buffer full specification is OFF
When the monitored data exceeds the monitor data area size, monitoring is continued by writing new data over the oldest
data.
When stop at buffer full specification is ON
When the monitor data area is full (monitor buffer size), monitoring is automatically stopped and "1002H" is written in the
send/receive data monitoring designation area. (Set by C24)
0 timer error outbreak stop designation (bit 2)
When the o timer error outbreak stop designation is OFF
Monitoring continues even if the timer 0 error (error code 7F40H) occurs.
When the 0 timer error outbreak stop designation is ON
When the timer 0 error (error code 7F40H) occurs, monitoring is automatically stopped and "1002H" is written in the send/
receive data monitoring designation area. (Set by C24)
Monitor buffer start address designation (Un\G8218/8474)
Designate the start address of the storage area (monitor data area) for the monitored data within the range of the user setting
area of the buffer memory.
Setting range: 0400H to 1AFDH, 2600H to 3FFDH (Default: 9728/13056 (2600H/3300H))
Monitor buffer size designation (Un\G8219/8475)
Designate the size of the monitor data area.
Setting range: 0003H to 1A00H (Default: 0D00H)
b15 b0
Buffer memory address (Default: 0000H)
Un\G8216/8472
Set the monitor start/stop.
0000H: No monitor/Monitor stop
0001H: Monitor start
0002H: Monitoring (Set by C24)
1002H: Monitor stop (Set by C24)
100FH: Monitor setting error (Set by C24)
to
001/01/0
b15 b0b2 b1b3
0H: OFF
1H: ON
0H: OFF
1H: ON
Buffer memory address
Un\G8217/8473
(Default: 0000H)
Stop by buffer full
Stop by timer 0 error
to

Table of Contents