PARAMETERS
97
<Setting 2>
Set these parameters to improve performance in the intelligent mode.
(
1
)
Pr. 61 "reference I for intelligent mode"
Setting Reference Current
9999 (factory setting) Referenced from rated inverter current
0 to 500A Referenced from setting (rated motor current)
(
2
)
Pr. 62 "reference I for intelligent mode acceleration"
The reference current setting can be changed.
Setting Reference Current
9999 (factory setting) 150% (180%) is the limit value.
0 to 200% The setting of 0 to 200% is the limit value.
(
3
)
Pr. 63 "reference I for intelligent mode deceleration"
The reference current setting can be changed.
Setting Reference Current
9999 (factory setting) 150% (180%) is the limit value.
0 to 200% The setting of 0 to 200% is the limit value.
Note: Pr. 61 to Pr. 63 are only valid when any of "1, 2, 11, 12" are selected for
Pr. 60.