3.4.3 Operation mode setting program example
Write programs as explained below to write various data to the inverters:
(
1
)
Operation mode switching program example
1) The following program changes the operation mode of station 2 inverter to CC-Link
operation.
Operation mode writing code number: FB
H
(hexadecimal)
CC-Link operation set data: 0000
H
(hexadecimal) (Refer to page 57.)
The reply code at the time of instruction code execution is set to D2. (Refer to
page 58.)
SET M303
M9036
FROM 0000 00E2 M200 2
PLS M302
M303
FROM 0000 02E6 D2 1
HH K
MOV 00FB
H
D100
TO 0000 01E6 D100 2
HH K
26
46
X0000 X000F X0001 X0020
M302
HH KK4
SET M115
M215
67
RST M115
RST M303
TO 0000 0162 M100
2
HHK4K
M9036
88
36
44
M202
MOV 0000
H
D101
Switches on the instruction code
execution request (RY2F).
Switches off the instruction code
execution request (RY2F).
Reads the remote input (RX20 to RX3F)
data of buffer memory to M200-M231.
Writes operation mode writing code (FB
H
)
to RWw
6
and set data (0000
H
) to RWw
7
.
Reads reply code (RWr
6
) to D2 when
the instruction code execution completion
(RX2F) switches on.
Writes M100-M131 data to the remote
outputs (RY20 to RY3F) of buffer memory.
Write setting Inverter running
*The switching result is stored into D2.
D2 = 0000
H
..........Normal completion of switching
0001
H
..........Write error
0002
H
..........Parameter selection error
0003
H
..........Setting range error
2) Operation mode setting
Code number: FB
H
Set data......... 0000
H
: CC-Link operation
0002
H
: PU operation
Note: PU operation cannot be set from the PLC.
The reply code at the time of instruction code execution is set to D2. (Refer to
page 58.)