Function name Description Corrective action Display
Major
fault
Overcurrent
trip during
acceleration
Overcurrent has occurred
during acceleration.
Set the acceleration time longer. (Shorten the
downward acceleration time in vertical lift application.)
If "E.OC1" always appears at start, disconnect the
motor once and restart the inverter. If "E.OC1" still
appears, the inverter may be faulty. Contact your sales
representative.
Check the wiring for output short circuit and ground fault.
When the rated motor frequency is 50Hz, set the Pr. 3
Base frequency to 50Hz.
Lower the stall prevention operation level.
Activate the stall prevention operation and the fast-
response current limit operation. (Pr.156)
For the operation with frequent regenerative driving,
set the base voltage (rated motor voltage, etc.) in Pr.
19 Base frequency voltage.
If the motor is coasting, stop the motor, then input a
start command. Alternatively, use the automatic restart
after instantaneous power failure/ying start function.
Overcurrent
trip during
constant
speed
Overcurrent has occurred
during constant speed
operation.
Keep the load stable.
Check the wiring to avoid output short circuit or ground
fault.
Lower the stall prevention operation level.
Activate the stall prevention operation and the fast-
response current limit operation. (Pr.156)
Overcurrent
trip during
deceleration
or stop
Overcurrent has occurred
during deceleration or at a
stop.
Set the deceleration time longer.
Check the wiring to avoid output short circuit or ground
fault.
Check if the mechanical brake is set to be activated
too early.
Lower the stall prevention operation level.
Activate the stall prevention operation and the fast-
response current limit operation. (Pr.156)
Regenerative
overvoltage
trip during
acceleration
Overvoltage has occurred
during acceleration.
Set the acceleration time shorter.
Use the regeneration avoidance function (Pr. 882, Pr.
883, Pr.885, Pr.886).
Set the Pr. 22 Stall prevention operation level correctly.