App.2-4
Function name Description Corrective action Display
Major
fault
Regenerative
overvoltage
trip during
constant
speed
Overvoltage has occurred
during constant speed
operation.
Keep the load stable.
Use the regeneration avoidance function (Pr. 882,
Pr. 883, Pr.885, Pr.886).
Use the brake resistor, brake unit or power
regeneration common converter (FR-CV) as required.
Set the Pr. 22 Stall prevention operation level correctly.
Regenerative
overvoltage
trip during
deceleration
or stop
Overvoltage has occurred
during deceleration or at a
stop.
Set the deceleration time longer. (Set the deceleration
time which matches the moment of inertia of the load.)
Make the brake cycle longer.
Use the regeneration avoidance function (Pr. 882, Pr.
883, Pr.885, Pr.886).
Use the brake resistor, brake unit or power
regeneration common converter (FR-CV) as required.
Inverter
overload trip
(electronic
thermal O/L
relay function)*
1
The electronic thermal
relay function for inverter
element protection has
been activated.
Set the acceleration/deceleration time longer.
Adjust the Pr. 0 Torque boost setting.
Set the Pr. 14 Load pattern selection setting according
to the load pattern of the using machine.
Reduce the load.
Set the surrounding air temperature to within the
specications.
Motor overload
trip
(electronic
thermal O/L
relay function)*
1
The electronic thermal relay
function for motor protection
has been activated.
Reduce the load.
For a constant-torque motor, set the constant-torque
motor in Pr. 71 Applied motor.
Set the stall prevention operation level accordingly.
Heatsink
overheat
The heatsink has
overheated.
Set the surrounding air temperature to within the
specications.
Clean the heatsink.
Replace the cooling fan.
Input phase
loss*
3
One of the three phases
on the inverter input side
has been lost. It may also
appear if phase-to-phase
voltage of the three-phase
power input has become
largely unbalanced.
Wire the cables properly.
Repair a break portion in the cable.
Check the Pr. 872 Input phase loss protection selection
setting.
Set Pr. 872 Input phase loss protection selection = "0"
(without input phase loss protection) when three-phase
input voltage is largely unbalanced.
Stall
prevention
stop
The output frequency has
dropped to 1Hz as a result
of deceleration due to the
excess motor load.
Reduce the load. (Check the Pr. 22 Stall prevention
operation level setting.)